the breaker at the remote end has been opened and the load flowing through has
therefore been disconnected. This current can be, for example, due to the charging
current of the phases or the load current of the tapped loads. The
Minimum current
setting value is set below the
Load current value setting. By default, the Minimum
current setting value is set to "0.05 pu".
The
Minimum current time setting is used to provide the start delay for the loss of
load current detection to avoid an unwanted release of the function. The value of
Minimum current time is by default set to "0.2 s".
5.9.7
Signals
5.9.7.1
DSTPLAL Input signals
Table 1176: DSTPLAL Input signals
Name
Type
Default
Description
I3P
SIGNAL
-
Three-phase currents
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
AR_READY
BOOLEAN
0=False
Autoreclosure ready,
releases function
used for fast trip
CB_CL_CMD
BOOLEAN
0=False
CB close command
EX_ACC
BOOLEAN
0=False
Connected to func-
tion used for tripping
at zone extension
LOSSLOAD_ACC
BOOLEAN
0=False
Connected to func-
tion used for tripping
at loss of load
NONDIR_ST
BOOLEAN
0=False
Non directional crite-
ria used to prevent in-
stantaneous trip
5.9.7.2
DSTPLAL Output signals
Table 1177: DSTPLAL Output signals
Name
Type
Description
OPR_LOSSLOAD
BOOLEAN
Operate by loss of load
OPR_Z_EXTN
BOOLEAN
Operate by zone extension
5.9.8
DSTPLAL Settings
1MRS759142 F
Protection related functions
REX640
Technical Manual
1235
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......