
Figure 674: Validation of PHIZ on sand
Figure 675: Validation of PHIZ on grass
5.4.6
Application
PHIZ is used to detect a downed conductor dropping to a very resistive ground,
causing an earth fault which is very difficult to detect by a conventional protection
relay functionality. PHIZ is then targeted to be used with overhead lines. PHIZ must
be used in electrical networks with efficiently grounded or isolated neutral.
Electric power lines experience faults for many reasons. In most cases, electrical
faults manifest in mechanical damage, which must be repaired before returning the
line to service.
Most of the electrical network faults are earth faults. Conventional protection
systems based on overcurrent, impedance or other principles are suitable for
detecting relatively low-impedance faults which have a relatively high fault current.
However, a small percentage of the earth faults have a very large impedance.
They are comparable to load impedance and consequently have very little fault
current. These high-impedance faults do not pose imminent danger to power
system equipment. However, they are a considerable threat to people and property.
The IEEE Power System Relay Committee working group on High Impedance Fault
Detection Technology defines High Impedance Faults as those that 'do not produce
enough fault current to be detectable by conventional overcurrent relays or fuses.
PHIZ always needs sensitive Io measurement.
High-impedance fault (PHIZ) detection requires a different approach than that for
conventional low-impedance faults. Reliable detection of PHIZ provides safety to
humans and animals. ABB has developed innovative technology for highimpedance
fault detection with over ten years of research resulting in many successful field
tests.
5.4.7
Signals
Protection related functions
1MRS759142 F
1182
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......