Figure 667: Functional module diagram
Timer
The duration of the
TRIP
output signal from TRPPTRC can be adjusted with the
Trip
pulse time setting when the "Non-latched" operation mode is used. The pulse length
should be long enough to secure the opening of the breaker. For three-pole tripping,
TRPPTRC has a single input
OPERATE
, through which all trip output signals are
routed from the protection functions within the protection relay, or from external
protection functions via one or more of the protection relay's binary inputs. The
function has a single trip output
TRIP
for connecting the function to one or more
of the protection relay's binary outputs, and also to other functions within the
protection relay requiring this signal.
The
BLOCK
input blocks the
TRIP
output and resets the timer.
Lockout logic
TRPPTRC is provided with possibilities to activate a lockout. When activated, the
lockout can be manually reset after checking the primary fault by activating the
RST_LKOUT
input or from the LHMI clear menu parameter. When using the "Latched"
mode, the resetting of the
TRIP
output can be done similarly as when using the
"Lockout" mode. It is also possible to reset the "Latched" mode remotely through a
separate communication parameter.
The minimum pulse trip function is not active when using the "Lockout"
or "Latched" modes but only when the "Non-latched" mode is selected.
The
CL_LKOUT
and
TRIP
outputs can be blocked with the
BLOCK
input.
Table 1123: Operation modes for the TRPPTRC trip output
Mode
Operation
Non-latched
The
Trip pulse length
parameter gives the
minimum pulse length for
TRIP
Latched
TRIP
is latched ; both local and remote clear-
ing is possible.
Lockout
TRIP
is locked and can be cleared only locally
via menu or the
RST_LKOUT
input.
Protection related functions
1MRS759142 F
1176
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......