POSCLOSE
Enable timer
From Start logic
CB failure mode ”Current”
CB failure mode ”Breaker
status”
CB failure mode ”Both(OR)”
AND
CB failure trip mode
”1 out of 3"
CB failure trip mode
”1 out of 4"
AND
AND
AND
CB failure trip mode
”2 out of 4"
OR
OR
AND
I >
From level detector 1
TRBU
I
0
>
From level detector 2
AND
OR
OR
OR
OR
CB failure mode ”Both(OR)”
AND
AND
BLOCK
Timer 2 elapsed
From Timer 2
CB_FAULT_AL
From Timer 3
AND
1, 2 or 3 ph
2 or 3 ph
OR
AND
CB failure mode ”Both(AND)”
Figure 664: Backup trip logic
5.2.6
Application
The n-1 criterion is often used in the design of a fault clearance system. This means
that the fault is cleared even if some component in the fault clearance system is
faulty. A circuit breaker is a necessary component in the fault clearance system. For
practical and economical reasons, it is not feasible to duplicate the circuit breaker
for the protected component, but breaker failure protection is used instead.
The breaker failure function issues a backup trip command to up-stream circuit
breakers in case the original circuit breaker fails to trip for the protected
component. The detection of a failure to break the current through the breaker
is made by measuring the current or by detecting the remaining trip signal
(unconditional).
CCBRBRF can also retrip. This means that a second trip signal is sent to the
protected circuit breaker. The retrip function is used to increase the operational
reliability of the breaker. The function can also be used to avoid backup tripping
of several breakers in case mistakes occur during protection relay maintenance and
tests.
1MRS759142 F
Protection related functions
REX640
Technical Manual
1171
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......