Characteristic
Value
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Operate time accuracy in definite
time mode
1 % of the theoretical value or ±20 ms
Operate time accuracy in inverse
definite minimum time mode
5 % of the theoretical value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2,3,4,5,..
4.12.3
Three-phase current unbalance protection for shunt
capacitor banks HCUBPTOC (ANSI 60P)
4.12.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase current unbalance pro-
tection for shunt capacitor banks
HCUBPTOC
3dI>C
60P
4.12.3.2
Function block
Figure 632: Function block symbol
4.12.3.3
Functionality
The three-phase current unbalance protection function for shunt capacitor banks
HCUBPTOC is used to protect the H-bridge capacitor banks against internal faults.
HCUBPTOC is suitable for protection of internally fused, externally fused and fuse-
less capacitor bank applications.
HCUBPTOC has two stages of operation, the operation stage and alarm stage.
In the operation stage, HCUBPTOC starts when the measured unbalance current
exceeds the set limit. The operating time characteristics can be selected to be
either definite time (DT) or inverse definite minimum time (IDMT). In the alarm
stage, the alarm starts when the measured unbalance current exceeds the set alarm
limit. The alarm time characteristics are based on DT.
HCUBPTOC contains blocking functionality. It is possible to block the function
outputs, timers or the function itself.
1
Fundamental frequency current = 1.0 × I
n
, current before fault = 0.0 × I
n
, fault current = 2.0 ×
Start
value, results based on statistical distribution of 1000 measurements
2
Includes the delay of the signal output contact
1MRS759142 F
Protection functions
REX640
Technical Manual
1131
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......