State
Power supply
module Ready
LED
LHMI Home
button
Alarm
acknowledged
Process related alarm has been ac-
tive earlier, but is not any more ac-
tive
Steady green
Steady green
Yes
Relay set to Test Mode
LF blinking green LF blinking green No
The physical SHMI Home button has two operation modes.
• On the SHMI’s navigation page, the Home button indicates the combined status
of all connected relays. If multiple relays have different statuses, the Home
button shows the indication with the highest priority.
• On the HMI view, the Home button indicates the status of the respective relay as
described in
3.3.4
Fail-safe principle for relay protection
The relay behavior during an internal fault situation has to be considered when
engineering trip circuits under the fail-safe principle. The considerations discussed
and examples given are mainly based on the need of protection scheme reliability.
The reliability need can be divided into two subparts: dependability and security.
The dependability can be described as the protection scheme’s ability to operate
when required. The security can be described as the protection scheme’s ability to
refrain from operating when not required. The protection scheme fail-safe principle
is typically related to satisfying these two performance criteria. Depending on the
requirements set to the electricity distribution process, one of the criteria may get
more attention than the other. However, in some industrial electricity distribution
networks, the main (productization) process is so dependent on reliable electricity
supply that both criteria are addressed equally.
The examples presented focus on the relay’s protection role in the fail-safe circuitry
using traditional hardwiring. If communication between the relays, or to an upper
level system, is a part of the fail-safe functionality, it must be also be a part of the
circuitry.
3.3.4.1
Motor feeder
The target is to prevent the motor from running uncontrollably and to secure the
emergency stop circuit functionality.
Basic functions
1MRS759142 F
110
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......