
Figure 561: Defined zones
The impedance is continuously monitored for detecting an out of step condition.
When the impedance enters inside from the outer blinder, the out of step detection
timer is triggered. If impedance remains between outer and inner blinder for the
duration of the
Swing time setting, output
SWING
is activated. If the impedance
enters the mho circle in zone 1, out of step blocking ( OSB) for zone 1 is detected
and output
OSB
is activated, or if the impedance enters the mho circle in zone 2, OSB
for zone 2 is detected and output
OSB_Z2
is activated if setting
Zone 2 enable is set
to “Yes”. Both
OSB
and
OSB_Z2
can be activated if the impedance passes through
zone 1 and zone 2 while inside the mho circle. The
OSB
or
OSB_Z2
output deactivates
when impedance exits and remains outside the mho circle and the inner blinder for
a duration of five cycles.
Activation of the
OPERATE
output depends on the
Oos operate mode selected. The
available options are “Way in”, “Way out”, and “Adaptive”. If the “Way in” option is
selected, the function triggers the delay timer after detecting an OSB condition.
When the set
Operate delay time has elapsed, the
OPERATE
output is activated.
When using the “Way in” option, the zone-related settings and zone slip counters are
not applicable.
If the “Way out” option is selected, after detecting an OSB condition, the function
further checks if impedance exits the outer blinder. On exiting the outer blinder, Way
out timer defined by
Operate delay time setting is triggered and the respective zone
slip counter is incremented after the set
Operate delay time has elapsed. If the slip
counter value is equal to the set number of slips in the respective enabled zone, the
OPERATE
output is activated. If the swing impedance passes through both zone 1
and zone 2, only the zone 1 slip counter is incremented. The zone 2 slip counter is
incremented if the impedance passes through the Mho circle but only through the
zone 2 portion. The zone 3 slip counter is incremented if the impedance misses the
1MRS759142 F
Protection functions
REX640
Technical Manual
1009
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......