empty or example configuration and make the proper selection
on the next page.
5.
On the
Version Selection
page, select the IEC 61850 version and click
Next
to
generate the functions.
6.
The
Summary
page shows the summary of the IED type, IP address and the
selected composition code. Click
Finish
to confirm the configuration and
conduct the insertion.
4.3.3
Inserting an IED from template directory
IED templates can be used to replicate IEDs with the same order code in PCM600
projects. The template includes an IED application configuration, graphical display
configuration (single-line diagram), communication protocol mappings and
parameters. An IED in the plant structure can be exported as a template (.pcmt file).
The template library can be built from all the exported IED templates.
It is also possible to insert an IED from the template library to create a new IED in the
plant structure. After a template IED has been imported,
IP address
and
Caption
in
IED's Object Properties and
Technical Key
of the physical IED have to be changed.
1.
In the
Plant Structure
view, select the bay, right-click, point to
New
and select
Create from template
.
A template IED can be inserted only when the bay is selected in
the plant structure.
2.
In the
Create New Object from Template
dialog box, select the IED under
Available Object Types
.
GUID-B44A7B25-EAAB-4FC5-8D48-843D026C6827 V1 EN
Figure 30:
PCM600: Selecting an IED from the template library
3.
Click the icon on the rightmost column in the list of available templates.
4.
In the
Template Properties
dialog box, verify the template information and
click
Close
.
Section 4
1MRS759117 A
Setting up a project
54
REX640
Engineering Manual