Table 20:
Test points for phase-to-phase loops L1-L2 (Ohm/Loop)
Test point
Reach
Set value
Comments
1
X
X1
set
R
0
2
X
X1
set
R
R1
set
3
X
0.8 x X1
set
R
0.8 x R1
set
+ RFPP/2
4
X
0.5 x X1
set
R
0.5 x R1
set
+ RFPP/2
5
X
0.85 x RFPP x tan (ArgRLd)
ArgRLd = angle for the maximal
load transfer
R
0.85 x RFPP
6
X
RLdFw x tan (ArgLd)
R
RLdFw
7
X
RLdFw x tan (ArgLd)
R
0
8
X
–0.2143 x RFPP/2
Exact: 0.8 x RFPP/2 (ArgDir)
R
0.8 x RFPP/2
9
X
–0.4 x RLdFw x tan(ArgDir)
R
0.4 x RLdFw
10
X
0.5 x X1
set
Exact –0.5 x R1
set
x
tan(ArgNegRes-90)
R
–0.23 x X1
set
11
X
0.8 x X1
set
Exact –0.5 x R1
set
x
tan(ArgNegRes-90)
R
–0.37 x X1
set
12
X
0.5 x X1
set
R
0.5 x R1
set
13
X
0
Only used when
OperationLdCmp
setting is 0 (Off)
R
0.5 x RFPP
Table 21:
Test points for phase-to-earth L3-E (Ohm/Loop)
Test point
Reach
Value
Comments
1
X
(2 x X1
set
+X0
set
)/3
R
0
2
X
(2 x X1
set
+ X0
set
)/3
R
2 x R1
set
+ R0
set
)/3
3
X
0.8 x (2 x X1
set
+ X0
set
)/3
R
0.8 x (2 x R1
set
+ R0
set
)/3 +RFPE
set
Table continues on next page
1MRK 504 088-UEN C
Section 13
Verifying settings by secondary injection
119
Installation and commissioning manual
Содержание RELION RET670
Страница 1: ...Relion 670 series Transformer protection RET670 Installation and commissioning manual...
Страница 2: ......
Страница 16: ...10...
Страница 24: ...18...
Страница 26: ...20...
Страница 28: ...22...
Страница 82: ...76...
Страница 88: ...82...
Страница 94: ...88...
Страница 104: ...98...
Страница 110: ...104...
Страница 210: ...204...
Страница 230: ...224...
Страница 239: ...233...