X1
R
X
(O/phase)
50%
80%
1
2
3
4
5
6
7
8
9
10
11
80% of RLdFwd
40% of RLdFwd
0.5 x RFPP
12
ANSI05000368-1-en.vsd
13
b
120°
20°
a
c
ANSI05000368 V1 EN
Figure 33:
Distance protection characteristic with test points for phase-to-phase
measurements
Table 28:
Test points for phase-to-phase loops A-B (Ohm/Loop)
Test point
Reach
Set value
Comments
1
X
X1
set
R
0
2
X
X1
set
R
R1
set
3
X
0.8 x X1
set
R
0.8 x R1
set
+ RFPPZx/2
4
X
0.5 x X1
set
R
0.5 x R1
set
+ RFPPZx/2
5
X
0.85 x RFPPZx x tan (LdAngle)
LdAngle = angle for the maximal load
transfer
R
0.85 x RFPPZx
6
X
RLdFwd x tan (LdAngle)
R
RLdFwd
7
X
0
R
RLdFw
8
X
–0.2143 x RFPPZx/2
Exact: 0.8 x RFPPZx/2 (ArgDir=20°)
R
0.8 x RFPPZx/2
Table continues on next page
1MRK 504 165-UUS -
Section 11
Testing functionality by secondary injection
Transformer protection RET670 2.2 ANSI
133
Commissioning manual