100 V
•
110 V
•
115 V
•
120 V
•
230 V
The IED fully supports all of these values and most of them will be shown in the
following examples.
4.2.4.3
Examples on how to connect a three phase-to-ground connected VT to
the IED
SEMOD55055-87 v9
gives an example on how to connect the three phase-to-ground connected
VT to the IED. It gives an overview of required actions by the user in order to make
this measurement available to the built-in protection and control functions within the
IED.
For correct terminal designations, see the connection diagrams valid for
the delivered IED.
Section 4
1MRK 504 163-UUS A
Analog inputs
88
Transformer protection RET670 2.2 ANSI
Application manual