Section 19
Metering
19.1
Pulse-counter logic PCFCNT
IP14600-1 v3
19.1.1
Identification
M14879-1 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Pulse-counter logic
PCFCNT
S00947 V1 EN-US
-
19.1.2
Application
M13395-3 v6
Pulse-counter logic (PCFCNT) function counts externally generated binary pulses, for
instance pulses coming from an external energy meter, for calculation of energy
consumption values. The pulses are captured by the binary input module (BIM), and
read by the PCFCNT function. The number of pulses in the counter is then reported via
the station bus to the substation automation system or read via the station monitoring
system as a service value. When using IEC 61850–8–1, a scaled service value is
available over the station bus.
The normal use for this function is the counting of energy pulses from external energy
meters. An optional number of inputs from an arbitrary input module in IED can be
used for this purpose with a frequency of up to 40 Hz. The pulse-counter logic
PCFCNT can also be used as a general purpose counter.
19.1.3
Setting guidelines
M13396-4 v9
Parameters that can be set individually for each pulse counter from PCM600:
•
Operation
:
Disabled
/
Enabled
•
tReporting
:
0-3600s
•
EventMask
:
NoEvents
/
ReportEvents
1MRK 504 163-UUS A
Section 19
Metering
Transformer protection RET670 2.2 ANSI
919
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...