9.4.3.6
Transformer application example
SEMOD55591-4 v8
Two main cases are of interest when residual overcurrent protection is used for a power
transformer, namely if residual current can be fed from the protected transformer
winding or not.
The protected winding will feed ground-fault (residual) current to ground faults in the
connected power system. The residual current fed from the transformer at external
phase-to-ground faults is highly dependent on the total positive and zero-sequence
source impedances. It is also dependent on the residual current distribution between the
network zero-sequence impedance and the transformer zero-sequence impedance. An
example of this application is shown in Figure
Section 9
1MRK 504 163-UUS A
Current protection
544
Transformer protection RET670 2.2 ANSI
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...