19.5.5
Monitored data
PID-6850-MONITOREDDATA v3
Table 499:
MU1_HW Monitored data
Name
Type
Values (Range)
Unit
Description
MUDATA
BOOLEAN
0=Ok
1=Error
-
Fatal error, data not received,
transmission errors, time-
sync issues or inconsistent
sample rate
SYNCH
BOOLEAN
0=Ok
1=Error
-
Operational mode on
ethernet link
SMPLLOST
BOOLEAN
1=Yes
0=No
-
Fatal error or recovery state
after fatal error. High if any
subscribed channel has bad
quality or TEST while IED not
in test mode.
MUSYNCH
BOOLEAN
0=Ok
1=Error
-
MU not synced or MU clock
not synced to same clock as
IED
TESTMODE
BOOLEAN
1=Yes
0=No
-
Quality of one or more
subscribed analogue
channels is TEST
SIMMODE
BOOLEAN
1=Yes
0=No
-
MU delivers simulated data
accepted by IED
BadReference
BOOLEAN
1=Yes
0=No
-
BadReference indication
output for I1
Derived
BOOLEAN
1=Yes
0=No
-
Derived indication output for
I1
Failure
BOOLEAN
1=Yes
0=No
-
Failure indication output for I1
Inaccurate
BOOLEAN
1=Yes
0=No
-
Inaccurate indication output
for I1
Inconsistent
BOOLEAN
1=Yes
0=No
-
Inconsistent indication output
for I1
OldData
BOOLEAN
1=Yes
0=No
-
OldData indication output for
I1
OperatorBlocked
BOOLEAN
1=Yes
0=No
-
OperatorBlocked indication
output for I1
Oscillatory
BOOLEAN
1=Yes
0=No
-
Oscillatory indication output
for I1
OutOfRange
BOOLEAN
1=Yes
0=No
-
OutOfRange indication output
for I1
Overflow
BOOLEAN
1=Yes
0=No
-
Overflow indication output for
I1
Source
BOOLEAN
0=Process
1=Substituted
-
Source indication output for
I1
Table continues on next page
Section 19
1MRK 511 408-UUS A
Station communication
654
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...