PID-6832-OUTPUTSIGNALS v3
Table 489:
GOOSESPRCV Output signals
Name
Type
Description
SPOUT
BOOLEAN
Single point output
DATAVALID
BOOLEAN
Data valid for single point output
COMMVALID
BOOLEAN
Communication valid for single point output
TEST
BOOLEAN
Test output
19.4.10.5
Settings
PID-6832-SETTINGS v3
Table 490:
GOOSESPRCV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
19.4.10.6
Operation principle
GUID-0E25A3FB-41BD-4EFE-9CA0-1262B9CD14CD v4
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
Data Value
Data Valid
Comm Valid
Test
Incoming data with q=Normal
Updated
1
1
0
Incoming data with q=oldData
0
0
1
0
Incoming data with q=Invalid
0
0
1
0
Incoming data with q=test
0
0
1
1
Incoming data with q=test+oldData
0
0
1
1
Receiver in block
0
0
1
0
Receiver in block and communication
error
0
0
0
0
Receiver in test mode and incoming
data with q= Normal
Updated
1
1
0
Receiver in test mode and incoming
data with q= Test
Updated
1
1
1
Communication Error
0
0
0
0
Section 19
1MRK 511 408-UUS A
Station communication
642
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...