Section 15
Logic
15.1
Tripping logic SMPPTRC (94)
IP14576-1 v4
15.1.1
Identification
SEMOD56226-2 v7
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Tripping logic
SMPPTRC
1 -> 0
IEC15000314 V1 EN-US
94
15.1.2
Functionality
M12275-3 v12
A function block for protection tripping and general start indication is always provided
as a basic function for each circuit breaker. It provides a settable pulse prolongation
time to ensure a trip pulse of sufficient length, as well as all functionality necessary for
correct co-operation with autoreclosing functions.
The trip function block includes a settable latch function for the trip signal and circuit
breaker lockout.
The trip function can collect start and directional signals from different application
functions. The aggregated start and directional signals are mapped to the IEC 61850
logical node data model.
1MRK 511 408-UUS A
Section 15
Logic
Phasor measurement unit RES670 2.2 ANSI
401
Technical manual