2.3.2
General device data
Table 4:
General device data
Object type Addr
IEC 61850 name
SA name
Description
Values
CTRL.LLN0
1
10
Loc.stVal
Local state
1=Local
LD0.LNN0
1
13
.SetSeld.stVal
Settings reserved
1=Reserved
1
14
.SetChg.stVal
Settings changed
1=Changed
DR.RDRE1
1
12
.RcdMade.stVal
DR recording made
1=Made
LD0.GSEGGIO1
1
15
.Alm.stVal
Goose Alarm
1=Alarm
LD0.LLN0
1
20
.PhyHealth1.stVal (Wrn)
Warning (one bit)
1=Warning
1
30
.PhyHealth2.stVal (IRF)
IRF (one bit)
1=IRF
LD0.LLN0
1
40001
.ActSG.stVal.SG1
Setting group 1 in use
1=In Use
1
40002
.ActSG.stVal.SG2
Setting group 2 in use
1=In Use
1
40003
.ActSG.stVal.SG3
Setting group 2 in use
1=In Use
1
40004
.ActSG.stVal.SG4
Setting group 3 in use
1=In Use
1
40005
.ActSG.stVal.SG5
Setting group 4 in use
1=In Use
1
40006
.ActSG.stVal.SG6
Setting group 5 in use
1=In Use
2.3.3
LD0.FPHLPTOC1 FA - Phase overcurrent protection, low
stage (1)
Table 5:
LD0.FPHLPTOC1 FA - Phase overcurrent protection, low stage (1)
Object type Addr
IEC 61850 name
SA name
Description
Values
LD0.FPHLPTOC1
1
1010
.Str.general
START
General start
1=Start
1
1011
.Str.phsA
phase A start
1=Start
1
1012
.Str.phsB
phase B start
1=Start
1
1013
.Str.phsC
phase C start
1=Start
1
1006
.Op.general
OPERATE
General operate
1=Operate
1
1007
.Op.phsA
phase A operate
1=Operate
1
1008
.Op.phsB
phase B operate
1=Operate
1
1009
.Op.phsC
phase C operate
1=Operate
Section 2
1MRS757824 C
IEC 60850-5-101/104 data mappings
16
Recloser Protection and Control RER615
Point List Manual