11.10
Elapsed time integrator with limit transgression and
overflow supervision TEIGGIO
11.10.1
Identification
Function Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2 device
number
Elapsed time integrator
TEIGGIO
-
-
11.10.2
Application
The function TEIGGIO is used for user defined logics and it can also be used for
different purposes internally in the IED . An application example is the integration of
elapsed time during the measurement of neutral point voltage or neutral current at
earth fault conditions.
Settable time limits for warning and alarm are provided. The time limit for overflow
indication is fixed.
11.10.3
Setting guidelines
The settings
tAlarm
and
tWarning
are user settable limits defined in seconds. The
achievable resolution of the settings depends on the level of the values defined.
A resolution of 10 ms can be achieved when the settings are defined within the range
1.00
second ≤
tAlarm
≤
99 999.99
seconds
1.00
second ≤
tWarning
≤
99 999.99
seconds.
If the values are above this range the resolution becomes lower
99 999.99
seconds ≤
tAlarm
≤
999 999.9
seconds
99 999.99
seconds≤
tWarning
≤
999 999.9
seconds
Note that
tAlarm
and
tWarning
are independent settings, that is, there
is no check if
tAlarm
>
tWarning
.
tOverflow
is for overflow supervision with a default value
tOverflow
=
999 999.9
seconds. The outputs freeze if an overflow occurs.
1MRK 505 291-UEN A
Section 11
Logic
257
Application manual
Содержание Relion REQ650
Страница 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Страница 2: ......
Страница 20: ...14 ...
Страница 26: ...20 ...
Страница 48: ...42 ...
Страница 82: ...76 ...
Страница 90: ...84 ...
Страница 160: ...154 ...
Страница 178: ...172 ...
Страница 264: ...258 ...
Страница 288: ...282 ...
Страница 302: ...296 ...
Страница 330: ...324 ...
Страница 338: ...332 ...
Страница 339: ...333 ...