circuit breakers. The autorecloser settings include the number of shots, first shot
combinations and many other useful settings.
9.3.10.2
Autorecloser SMBRREC (79)
Main menu/Settings/Setting Group N/Control/AutoRecloser(RREC,79)/AR
Displays available instances of the autorecloser function SMBRREC (79) with several
settable parameters per instance. There are settings for operation, number of shots,
open times and various threshold values.
9.3.10.3
synchronism-check and energizing check SESRSYN (25)
Main menu/Settings/Setting Group N/Control/Synchronizing(RSYN,25)/SYN
Displays available instances of the synchronism-check function SESRSYN (25) with
several settings per instance. There are settings for operation, voltage differences and
limits, time delays etc.
9.3.11
Monitoring
9.3.11.1
Overview
Event counter and fault locator settings are found under Monitoring in the Setting
Group N menu.
9.3.11.2
Event counter CNTGGIO
Main menu/Setting/Setting group N/Monitoring/EventCounter(GGIO)/CNT
Here the function can be set on or off.
9.3.11.3
Fault locator LMBRFLO
Main menu/Settings/Setting group N/Monitoring/FaultLocator(RFLO)
Setting data entered here are the various measured or calculated impedances and
resistances of the protected line section. This data may be physically measured or taken
from computer simulation studies of the Line segment. For example the parameters
R1A and X1A are the resistance and reactance in reverse direction, the parameters R1B
and X1B are the resistance and reactance in the forward direction. These parameters
along with the others found here need to be given values. For complete parameter data
refer to the Technical reference manual (TRM).