85
Distance protection
Chapter 11
Verifying settings by secondary
injection
Table 16:
Test points for phase-to-earth L3-E (Ohm/Loop)
9
X
–0.4 x RLdFw x tan(ArgDir)
R
0.4 x RLdFw
10
X
0.5 x X1
set
Exact –0.5 x R1
set
x tan(ArgNegRes-90)
R
–0.23 x X1
set
11
X
0.8 x X1
set
Exact –0.5 x R1
set
x tan(ArgNegRes-90)
R
–0.37 x X1
set
12
X
0.5 x X1
set
R
0.5 x R1
set
13
X
0
Only used when
OperationLdCmp
setting is 0 (Off)
R
0.5 x RFPP
Test point
Reach
Set value
Comments
Test point
Reach
Value
Comments
1
X
(2 x X1
set
+X0
set
)/3
R
0
2
X
(2 x X1
set
+ X0
set
)/3
R
2 x R1
set
+ R0
set
)/3
3
X
0.8 x (2 x X1
set
+ X0
set
)/3
R
0.8 x (2 x R1
set
+ R0
set
)/3 +RFPE
set
4
X
0.5 x (2 x X1
set
+ R0
set
)/3
R
0.5 x (2 x R1
set
+R0
set
)/3 + RFPE
set
5
X
0.85 x RFPE
set
x tan(ArgLdset)
ArgLd = angle for the maximal load transfer.
R
0.85 x RFPE
6
X
RLdFwset x tan(ArgLdSet)
R
RLdFw
set
7
X
0
R
RLdFw
set
8
X
–02143 x RLdFw
set
Exact: 0.8 x RFPE x tan (ArgDir)
R
0.8 x RLdFw
set
9
X
–0.8 x RLdFw
set
x tan(ArgDir)
R
0.8 x RLdFw
set
10
X
0.17 x (2 x X1
set
+ X0
set
)
Exact: 0.5 x (2 x X1
set
X0
set
)/3
R
-0.36 x (2 x X1
set
+ X0
set
)
Exact: 0.5 x (2X1
set
+ X0
set
)/(3 x tan(AgNegDir90)
Содержание RELION REL670
Страница 8: ...Contents ...
Страница 54: ...46 Checking the optical connections Chapter 6 Checking the external optical and electrical connections ...
Страница 72: ...64 About this chapter Chapter 9 Establishing connection and verifying the LON communication ...
Страница 78: ...70 Downloading settings and configuration from a PC Chapter 10 Configuring the IED and changing settings ...
Страница 174: ...166 Remote communication Chapter 11 Verifying settings by secondary injection ...
Страница 190: ...182 Maintenance Chapter 13 Fault tracing and repair ...
Страница 198: ...190 Glossary Chapter 14 Glossary ...