OPEN_EN
POSOPEN
POSCLOSE
1
EN_OPEN
EN_CLOSE
CLOSE_EN
SCILO
=1
&
>1
>1
&
&
&
en04000525.vsd
IEC04000525 V1 EN
Figure 308:
SCILO function logic diagram
14.2.4
Interlocking for busbar earthing switch BB_ES
14.2.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for busbar earthing switch
BB_ES
-
3
14.2.4.2
Functionality
The interlocking for busbar earthing switch (BB_ES) function is used for one busbar
earthing switch on any busbar parts according to figure
.
QC
en04000504.vsd
IEC04000504 V1 EN
Figure 309:
Switchyard layout BB_ES
1MRK502052-UEN B
Section 14
Control
649
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...