
9.1.8
Technical data
Table 269:
UV2PTUV technical data
Function
Range or value
Accuracy
Operate voltage, low
and high step
(1.0–100.0)% of
UBase
±0.5% of U
r
Absolute hysteresis
(0.0–50.0)% of
UBase
±0.5% of U
r
Internal blocking
level, step 1 and step
2
(1–50)% of
UBase
±0.5% of U
r
Inverse time
characteristics for
step 1 and step 2, see
-
Definite time delay,
step 1 at 1.2 to 0 x
U
set
(0.00-6000.00) s
±0.2% or ±40ms whichever is
greater
Definite time delay,
step 2 at 1.2 to 0 x
U
set
(0.000-60.000) s
±0.2% or ±40ms whichever is
greater
Minimum operate
time, inverse
characteristics
(0.000–60.000) s
±0.2% or ±40ms whichever is
greater
Operate time, start at
2 to 0 x U
set
Min= 15 ms
Max= 30 ms
-
Reset time, start at 0
to 2 x U
set
Min= 15 ms
Max= 30 ms
-
Operate time, start at
1.2 to 0 x U
set
Min= 5 ms
Max= 25 ms
-
Reset time, start at 0
to 1.2 x U
set
Min= 15 ms
Max= 35 ms
-
Critical impulse time
5 ms typically at 1.2 to 0 x U
set
-
Impulse margin time
15 ms typically
-
9.2
Two step overvoltage protection OV2PTOV
9.2.1
Identification
Function description
IEC 61850
identification
IEC 60617 identification
ANSI/IEEE C37.2
device number
Two step overvoltage protection
OV2PTOV
3U>
SYMBOL-C-2U-SMALLER-THAN V2 EN
59
1MRK502052-UEN B
Section 9
Voltage protection
491
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...