In version 2.0, a typical starting time delay of 24ms is subtracted from
the set trip time delay, so that the resulting trip time will take the
internal IED start time into consideration.
25.3
Inverse characteristics
Table 959:
ANSI Inverse time characteristics
Function
Range or value
Accuracy
Operating characteristic:
(
)
1
P
A
t
B k tDef
I
æ
ö
ç
÷
=
+
× +
ç
÷
ç
-
÷
è
ø
EQUATION1249-SMALL V2 EN
Reset characteristic:
( )
2
1
=
×
-
tr
t
k
I
EQUATION1250-SMALL V1 EN
I = I
measured
/I
set
k = (0.05-2.00) in steps of 0.01 ANSI/IEEE C37.112 ,
± 2.0% or ± 40 ms
whichever is greater
ANSI Extremely Inverse
A=28.2, B=0.1217, P=2.0 ,
tr=29.1
ANSI Very inverse
A=19.61, B=0.491, P=2.0 ,
tr=21.6
ANSI Normal Inverse
A=0.0086, B=0.0185, P=0.02,
tr=0.46
ANSI Moderately Inverse
A=0.0515, B=0.1140, P=0.02,
tr=4.85
ANSI Long Time Extremely Inverse
A=64.07, B=0.250, P=2.0,
tr=30
ANSI Long Time Very Inverse
A=28.55, B=0.712, P=2.0,
tr=13.46
ANSI Long Time Inverse
A=0.086, B=0.185, P=0.02,
tr=4.6
1MRK502052-UEN B
Section 25
Inverse time characteristics
1253
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...