On all access points, the
PTP
parameter is “
ON
”.
On the REL, the parameter
FineSyncSource
(under
Configuration/Time/
Synchronization/TIMESYNCHGEN:1/General
) is set to “
GPS
” if there is a GPS
antenna attached.
If the GTM is used as a PPS output only, the
FineSynchSource
is not set.
23.13.2.3
Process bus IEC/UCA 61850-9-2LE synchronization
When process bus communication (IEC/UCA 61850-9-2LE protocol) is used, it is
essential that the merging units are synchronized with the hardware time of the IED
(see Technical manual, section
Design of the time system (clock synchronization
) ). To
achieve this, PTP, PPS or IRIG-B can be used depending of the facilities of the
merging unit.
If the merging unit supports PTP, use PTP. If PTP is used in the IED and the merging
unit is not PTP capable, then synchronize the merging unit from the IED via a PPS out
from the GTM. If PTP is used in the IED and the merging unit cannot be synchronized
from the IED, then use GPS-based clocks to provide PTP synch as well as sync to the
merging unit.
If synchronization of the IED and the merging unit is based on GPS, set the parameter
LostSyncMode
to
BlockOnLostUTC
in order to provide a block of protection functions
whenever the global common time is lost.
If PTP is not used, use the same synchronization method for the
HwSyncSrc
as the
merging unit provides. For instance, if the merging unit provides PPS as
synchronization, use PPS as
HwSyncSrc
. If either PMU or LDCM in GPS-mode is
used, that is, the hardware and software clocks are connected to each other,
HwSyncSrc
is not used and other means to synchronize the merging unit to the IED is
required. Either
FineSyncSource
is set to the same source that the merging unit uses,
or the PPS output from the GTM module is used to synchronize the merging unit. If
the PPS output from the GTM module is used to synchronize the merging unit and PTP
is not used, the IED does not know how the merging unit is synchronized and the
parameter
LostSyncMode
must be set to
NoBlock
.
Section 23
1MRK 502 071-UEN -
Basic IED functions
742
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...