9.15.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Generator stator overload protection
GSPTTR
49S
9.15.2
Application
Overload protection for stator, GSPTTR.
The overload protection GSPTTR is intended to prevent thermal damage. A generator
may suffer thermal damage as a result of overloads. Damage is the result when one or
more internal generator components exceeds its design temperature limit. Damage to
generator insulation can range from minor loss of life to complete failure, depending
on the severity and duration of the temperature excursion. Excess temperature can also
cause mechanical damage due to thermal expansion. Temperature rise with in a
generator for these conditions is primarily a function of I
2
R copper losses. Because
temperature increases with current, it is logical to apply overcurrent elements with
inverse time-current characteristics. The generator overcurrent applications are
complicated by the complexity of generator thermal characteristics and the time-
varying nature of current experienced during starting and when the generator drives a
time-varying load.
The generator stator overload function GSPTTR protects stator windings against
excessive temperature rise as result of overcurrents.
9.16
Generator rotor overload protection GRPTTR
9.16.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Generator rotor overload protection
GRPTTR
49R
9.16.2
Application
The overload GRPTTR protection is intended to prevent thermal damage. A generator
may suffer thermal damage as a result of overloads. Damage is the result when one or
more internal generator components exceeds its design temperature limit. Damage to
generator insulation can range from minor loss of life to complete failure, depending
on the severity and duration of the temperature excursion. Excess temperature can also
cause mechanical damage due to thermal expansion. Rotor components such as bars
and end rings are vulnerable to this damage. Temperature rise within a generator for
Section 9
1MRK 502 071-UEN -
Current protection
400
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...