Section 1
Operate
conditionally
UnrestrainedLimit
Section 2
Section 3
Restrain
Operate
unconditionally
5
4
3
2
1
0
0
1
2
3
4
5
IdMin
EndSection1
EndSection2
restrain current
[ times IBase ]
operate current
[ times IBase ]
SlopeSection2
SlopeSection3
en05000187-2.vsd
IEC05000187 V2 EN
Figure 53:
Representation of the restrained, and the unrestrained operate
characteristics
100%
Ioperate
slope
Irestrain
D
= D
×
EQUATION1246 V1 EN
(Equation 16)
and where the restrained characteristic is defined by the settings:
1.
IdMin
2.
EndSection1
3.
EndSection2
4.
SlopeSection2
5.
SlopeSection3
7.1.3.2
Elimination of zero sequence currents
A differential protection may operate undesirably due to external earth-faults in cases
where the zero sequence current can flow on only one side of the power transformer,
but not on the other side. This is the case when zero sequence current cannot be
properly transformed to the other side of the power transformer. Power transformer
1MRK 502 071-UEN -
Section 7
Differential protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
131
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...