9.4.2
Function block
GUID-222CC574-D72D-4426-876C-526D7C264C1E V1 EN
Figure 269:
Function block
9.4.3
Functionality
The multipurpose generic up-down counter function CTR counts up or down for each
positive edge of the corresponding inputs. The counter value output can be reset to zero or
preset to some other value if required.
The function provides up-count and down-count status outputs, which specify the relation
of the counter value to a loaded preset value and to zero respectively.
9.4.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
The operation of CTR can be described with a module diagram. All the modules in the
diagram are explained in the next sections.
GUID-9D9880AB-4CA7-4DD5-BA0C-C1D958FC04F6 V1 EN
Figure 270:
Functional module diagram
Up-down counter
Each rising edge of the
UP_CNT
input increments the counter value
CNT_VAL
by one and
each rising edge of the
DOWN_CNT
input decrements the
CNT_VAL
by one. If there is a
rising edge at both the inputs
UP_CNT
and
DOWN_CNT
, the counter value
CNT_VAL
is
unchanged. The
CNT_VAL
is available in the monitored data view.
1MRS240050-IB C
Section 9
Control functions
REF615R
511
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...