9.2.3.4
Thermal overload blocking
An alarm or pickup signal from the thermal overload protection 49F can be routed to the
input
BLK_THERM
to block and hold the reclose sequence. The
BLK_THERM
signal does
not affect the starting of the sequence. When the reclose time has elapsed and the
BLK_THERM
input is active, the shot is not ready until the
BLK_THERM
input deactivates.
Should the
BLK_THERM
input remain active longer than the time set by the setting
Max
block time
, the AR function goes to lockout.
If the
BLK_THERM
input is activated when the auto wait timer is running, the auto wait
timer is reset and the timer restarted when the
BLK_THERM
input deactivates.
9.2.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
The reclosing operation can be enabled and disabled with the
Reclosing operation
setting.
This setting does not disable the function, only the reclosing functionality. The setting has
three parameter values: “Enable”, “External Ctl” and ”Disable”. When the setting value
“External Ctl” is selected, the reclosing operation is controlled with the
RECL_ON
input.
The operation of 79 can be described using a module diagram. All the modules in the
diagram are explained in the next sections.
Section 9
1MRS240050-IB C
Control functions
460
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...