7.1.12.3
Signals
Table 336:
f Input signals
Name
Type
Default
Description
F
SIGNAL
-
Measured system frequency
7.1.12.4
Settings
Table 337:
f Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
F Hi high limit
35.00...75.00
Hz
60.00
High alarm frequency limit
F high limit
35.00...75.00
Hz
55.00
High warning frequency limit
F low limit
35.00...75.00
Hz
45.00
Low warning frequency limit
F Lo low limit
35.00...75.00
Hz
40.00
Low alarm frequency limit
F deadband
100...100000
1000
Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)
7.1.12.5
Monitored data
Table 338:
f Monitored data
Name
Type
Values (Range)
Unit
Description
f-Hz
FLOAT32
35.00...75.00
Hz
Measured frequency
7.1.12.6
Technical data
Table 339:
f Technical data
Characteristic
Value
Operation accuracy
±10 mHz
(in measurement range 35...75 Hz)
Section 7
1MRS240050-IB C
Measurement functions
412
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...