6.1.8
Monitored data
Table 278:
52CM Monitored data
Name
Type
Values (Range)
Unit
Description
T_TRV_OP
FLOAT32
0...60000
ms
Travel time of the CB during
opening operation
T_TRV_CL
FLOAT32
0...60000
ms
Travel time of the CB during
closing operation
T_SPR_CHR
FLOAT32
0.00...99.99
s
The charging time of the CB
spring
NO_OPR
INT32
0...99999
Number of CB operation cycle
INA_DAYS
INT32
0...9999
The number of days CB has
been inactive
CB_LIFE_A
INT32
-9999...9999
CB Remaining life phase A
CB_LIFE_B
INT32
-9999...9999
CB Remaining life phase B
CB_LIFE_C
INT32
-9999...9999
CB Remaining life phase C
IPOW_A
FLOAT32
0.000...30000.00
0
Accumulated currents power
(Iyt), phase A
IPOW_B
FLOAT32
0.000...30000.00
0
Accumulated currents power
(Iyt), phase B
IPOW_C
FLOAT32
0.000...30000.00
0
Accumulated currents power
(Iyt), phase C
52CM
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
6.1.9
Technical data
Table 279:
52CM Technical data
Characteristic
Value
Current measuring accuracy
±1.5% or ±0.002 × I
n
(at currents in the range of 0.1…10 × I
n
)
±5.0%
(at currents in the range of 10…40 × I
n
)
Operate time accuracy
±1.0% of the set value or ±20 ms
Travelling time measurement
+10 ms / -0 ms
1MRS240050-IB C
Section 6
Supervision functions
REF615R
361
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...