5.3.2
Function block
A071286-ANSI V2 EN
Figure 161:
Function block
5.3.3
Functionality
The master trip function 86/94 is intended to be used as a trip command collector and
handler after the protection functions. The features of this function influence the trip
signal behavior of the circuit breaker. The minimum trip pulse length can be set when the
non-latched mode is selected. It is also possible to select the latched or lockout mode for
the trip signal.
5.3.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
When the 86/94 function is disabled, all trip outputs which are intended to
go through the function to the circuit breaker trip coil are blocked.
The operation of 86/94 can be described with a module diagram. All the modules in the
diagram are explained in the next sections.
A070882-ANSI V2 EN
Figure 162:
Functional module diagram
Timer
The duration of a trip output signal from 86/94 can be adjusted with the
Trip pulse time
setting when the "Non-latched" operation mode is used. The pulse length should be long
enough to secure the opening of the breaker. For three-pole tripping, 86/94 has a single
1MRS240050-IB C
Section 5
Protection-related functions
REF615R
329
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...