Level detector
The measured ground voltage is compared to the set
Pickup value
. If the value exceeds the
set
Pickup value
, the level detector sends an enable signal to the timer.
Timer
Once activated, the timer activates the
PICKUP
output. The time characteristic is
according to DT. When the operation timer has reached the value set by
Trip delay time
,
the
TRIP
output is activated. If the fault disappears before the module trips, the reset timer
is activated. If the reset timer reaches the value set by
Reset delay time
, the operation timer
resets and the
PICKUP
output is deactivated.
The timer calculates the pickup duration value PICKUP_DUR, which indicates the ratio
of the pickup situation and the set trip time. The value is available in the monitored data
view.
Blocking logic
There are three operation modes in the blocking function. The operation modes are
controlled by the
BLOCK
input and the global setting in
Configuration/System/Blocking
mode
which selects the blocking mode. The
BLOCK
input can be controlled by a binary
input, a horizontal communication input or an internal signal of the protection relay's
program. The influence of the
BLOCK
signal activation is preselected with the global
setting
Blocking mode
.
The
Blocking mode
setting has three blocking methods. In the "Freeze timers" mode, the
operation timer is frozen to the prevailing value, but the
TRIP
output is not deactivated
when blocking is activated. In the "Block all" mode, the whole function is blocked and the
timers are reset. In the "Block TRIP output" mode, the function operates normally but the
TRIP
output is not activated.
4.2.3.5
Application
59G is designed to be used for ground-fault protection in isolated neutral, resistance
grounded or reactance grounded systems. In compensated networks, the pickup of the
function can be used to control the switching device of the neutral resistor. The function
can also be used for the back-up protection of feeders for busbar protection when a more
dedicated busbar protection would not be justified.
In compensated and isolated neutral systems, the system neutral voltage, that is, the
ground voltage, increases in case of any fault connected to ground. Depending on the type
of the fault and the fault resistance, the ground voltage reaches different values. The
highest ground voltage, equal to the phase-to-ground voltage, is achieved for a single-
phase ground fault. The ground voltage increases approximately the same amount in the
whole system and does not provide any guidance in finding the faulty component.
1MRS240050-IB C
Section 4
Protection functions
REF615R
239
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...