4.2.3.2
Function block
GUID-F809C4BA-65E7-46D0-A46A-F51E7B90F1BA-ANSI V1 EN
GUID-AC9C406F-1A77-4135-A0A4-6F726EB18E1E V1 EN
Figure 113:
Function block
4.2.3.3
Functionality
The residual overvoltage protection function 59G/N is used in distribution networks
where the ground overvoltage can reach non-acceptable levels in, for example, high
impedance grounding.
The function picks up when the ground voltage exceeds the set limit. 59G/N operates with
the definite time (DT) characteristic.
The function contains a blocking functionality. It is possible to block function outputs, the
definite timer or the function itself, if desired.
4.2.3.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
The operation of 59G/N can be described by using a module diagram. All the modules in
the diagram are explained in the next sections.
GUID-852F56DB-266E-4CB8-BC58-01D4BA605FD0-ANSI V1 EN
Figure 114:
Functional module diagram
Section 4
1MRS240050-IB C
Protection functions
238
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...