4.1.9
Loss of phase 37
4.1.9.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Loss of phase
PHPTUC
3I<
37
4.1.9.2
Function block
GUID-ED7916D7-8083-4660-B274-252DA7DCB833-ANSI V1 EN
Figure 105:
Function block
4.1.9.3
Functionality
The loss of phase function 37 is used to detect an undercurrent that is considered as a fault
condition.
37 picks up when the current is less than the set limit. Operation time characteristics are
according to definite time (DT).
The function contains a blocking functionality. It is possible to block function outputs and
reset the definite timer if desired.
4.1.9.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
The operation of 37 can be described with a module diagram. All the modules in the
diagram are explained in the next sections.
Section 4
1MRS240050-IB C
Protection functions
218
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...