A070982-ANSI V1 EN
Figure 58:
Functionality of numerical multiple-stage overcurrent protection
The coordination plan is an effective tool to study the operation of time selective operation
characteristics. All the points mentioned earlier, required to define the overcurrent
protection parameters, can be expressed simultaneously in a coordination plan. In
, the coordination plan shows an example of operation characteristics in the LV-side
incoming feeder and radial outgoing feeder.
Section 4
1MRS240050-IB C
Protection functions
124
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...