TCSSCBR1
BLOCK
ALARM
TCSSCBR2
BLOCK
ALARM
OR
B1
B2
O
TCSSCBR1_ALARM
TCSSCBR1_ALARM
TCSSCBR2_ALARM
TCSSCBR2_ALARM
TCSSCBR_BLOCKING
TCSSCBR_BLOCKING
TCSSCBR_ALARM
GUID-D9B2A8EF-4B42-48D5-AD1D-E4A5131C2874 V1 EN
Figure 580:
Trip circuit supervision function
OR6
B1
B2
B3
B4
B5
B6
O
TRPPTRC2_TRIP
X120_BI3_CB_OPENED
TRPPTRC1_TRIP
TCSSCBR_BLOCKING
GUID-CABC7A2A-8406-44EA-8AE9-34E3EB7B1FA6 V1 EN
Figure 581:
Logic for blocking of trip circuit supervision function
3.14.3.4
Functional diagrams for control and interlocking
Two types of disconnector and earthing switch function blocks are available.
DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and
ESXSWI1 are controllable type. By default, the status only blocks are connected in the
standard configuration. The disconnector (CB truck) and line side earthing switch
status information are connected to DCSXSWI1 and ESSXSI1.
DCSXSWI1
POSOPEN
POSCLOSE
OPENPOS
CLOSEPOS
OKPOS
DCSXSWI1_OKPOS
X110_BI6_CB_TRUCK_IN_TEST
X110_BI5_CB_TRUCK_IN_SERVICE
GUID-88089155-4117-4BF7-BEAD-8EB5D61595E1 V1 EN
Figure 582:
Disconnector control logic
ESSXSWI1
POSOPEN
POSCLOSE
OPENPOS
CLOSEPOS
OKPOS
ESSXSWI1_OPENPOS
X110_BI8_ES1_OPENED
X110_BI7_ES1_CLOSED
GUID-52A1CCBB-9AD0-467E-9673-72905B03507C V
Figure 583:
Earthing-switch control logic
The circuit breaker closing is enabled when the
ENA_CLOSE
input is activated. The
input can be activated by the configuration logic, which is a combination of the
1MRS756378 S
Section 3
REF615 standard configurations
REF615
369
Application Manual