The IED offers six different settings groups which can be set based on individual
needs. Each group can be activated or deactivated using the setting group settings
available in the IED.
Depending on the communication protocol the required function block needs to be
instantiated in the configuration.
3.11.3.1
Functional diagrams for protection
The functional diagrams describe the IEDs protection functionality in detail and
according to the factory set default connections.
Four overcurrent stages are offered for overcurrent and short-circuit protection. Three
of these include directional functionality DPHxPDOC. Three-phase non-directional
overcurrent protection, instantaneous stage, PHIPTOC1 can be blocked by energizing
the binary input X120:BI1.
PHIPTOC1
BLOCK
ENA_MULT
OPERATE
START
PHIPTOC1_OPERATE
PHIPTOC1_START
X120_BI1_EXT_OC_BLOCKING
GUID-B16AE694-A1BF-450D-AFA8-BE6CDEC14F31 V1 EN
Figure 386:
Overcurrent protection function
DPHHPDOC1
BLOCK
ENA_MULT
NON_DIR
OPERATE
START
DPHLPDOC1
BLOCK
ENA_MULT
NON_DIR
OPERATE
START
DPHLPDOC2
BLOCK
ENA_MULT
NON_DIR
OPERATE
START
OR6
B1
B2
B3
B4
B5
B6
O
DPHLPDOC2_OPERATE
DPHLPDOC2_OPERATE
DPHHPDOC1_OPERATE
DPHHPDOC1_OPERATE
DPHLPDOC1_OPERATE
DPHLPDOC1_OPERATE
DPHLPDOC1_START
DPHLPDOC2_START
DPHHPDOC1_START
DPHxPDOC_OPERATE
GUID-D8B8656A-F5D7-4449-94B4-CFE402EDE482 V1 EN
Figure 387:
Directional overcurrent protection function
Section 3
1MRS756378 S
REF615 standard configurations
262
REF615
Application Manual