Channel
ID text
Level trigger mode
22
INRPHAR1 - blk2h
Level trigger off
23
T1PTTR1 - operate
Level trigger off
24
ARCSARC1 - ARC flt det
Level trigger off
ARCSARC2 - ARC flt det
ARCSARC3 - ARC flt det
25
ARCSARC1 - operate
Positive or Rising
26
ARCSARC2 - operate
Positive or Rising
27
ARCSARC3 - operate
Positive or Rising
28
DARREC1 - inpro
Level trigger off
29
DARREC1 - close CB
Level trigger off
30
DARREC1 - unsuc recl
Level trigger off
31
X120BI1 - ext OC blocking
Level trigger off
32
X120BI2 - CB closed
Level trigger off
33
X120BI3 - CB opened
Level trigger off
3.5.3
Functional diagrams
The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements.
The analog channels have fixed connections to the different function blocks inside the
IED’s standard configuration. However, the 12 analog channels available for the
disturbance recorder function are freely selectable as a part of the disturbance
recorder’s parameter settings.
The phase currents to the IED are fed from a current transformer. The residual current
to the IED is fed from either residually connected CTs, an external core balance CT,
neutral CT or internally calculated.
The IED offers six different settings groups which can be set based on individual
needs. Each group can be activated or deactivated using the setting group settings
available in the IED.
Depending on the communication protocol the required function block needs to be
instantiated in the configuration.
3.5.3.1
Functional diagrams for protection
The functional diagrams describe the IEDs protection functionality in detail and
according to the factory set default connections.
Four non-directional overcurrent stages are offered for overcurrent and short-circuit
protection. Three-phase non-directional overcurrent protection, instantaneous stage,
PHIPTOC1 can be blocked by energizing the binary input X120:BI1.
1MRS756378 S
Section 3
REF615 standard configurations
REF615
101
Application Manual