13.1.3.2
All indication LEDs
Activating the Reset of indication LEDs will zero all fifteen LEDs to the right of
the LCD.
Main mnenu/Reset/Reset LEDs/All indication LEDs
In the dialog box that appears, choose YES to reset.
13.1.4
Reset lockout SMPPTRC
Objects that are considered at risk after a trip may be prevented from reconnecting
by a lockout condition. The reset lockout facility is used to undo a lockout
condition caused by a such a trip.
Main menu/Reset/Reset lockout/TripLogic(PTRC,94)/TRP
In the dialog box that appears, choose YES to reset.
13.1.5
Reset process eventlist
Main menu/Reset/Reset process eventlist
Local HMI setting for resetting the process eventlist.
13.1.6
Reset temperature functions
The Reset temperature function under the Reset counters menu offers the following
reset possibilities. These are outlined below.
Main menu/Reset/Reset temperature/ThermalOverload1TimeConstant(PTTR,
26)/THL
In the dialog box that appears, choose YES to reset.
Main menu/Reset/Reset temperature/ThermalOverload2TimeConstant(PTTR,
49)/THL
In the dialog box that appears, choose YES to reset.
1MRK 511 188-UEN C
Section 13
Reset
95
Operator's manual