14.4.7.2
Signals in single breaker arrangement
M15053-6 v5
The busbar grounding switch is only allowed to operate if all disconnectors of the bus-
section are open.
en04000505_ansi.vsd
Section 1
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
AB_TRAFO
ABC_LINE
BB_ES
ABC_LINE
(WA1)A1
(WA2)B1
(WA7)C
C
B2
A2
BB_ES
ABC_BC
ANSI04000505 V1 EN-US
Figure 159:
Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
BB_DC_OP
All disconnectors on this part of the busbar are open.
VP_BB_DC
The switch status of all disconnector on this part of the busbar is valid.
EXDU_BB
No transmission error from any bay containing the above information.
These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO),
and each bus-coupler bay (ABC_BC) are needed:
Signal
189OPTR
189 is open.
289OPTR
289 is open (AB_TRAFO, ABC_LINE)
22089OTR
289 and 2089 are open (ABC_BC)
789OPTR
789 is open.
VP189TR
The switch status of 189 is valid.
VP289TR
The switch status of 289 is valid.
V22089TR
The switch status of 289and 2089 is valid.
VP789TR
The switch status of 789 is valid.
EXDU_BB
No transmission error from the bay that contains the above information.
These signals from each bus-section disconnector bay (A1A2_DC) are also needed.
For B1B2_DC, corresponding signals from busbar B are used. The same type of
module (A1A2_DC) is used for different busbars, that is, for both bus-section
disconnectors A1A2_DC and B1B2_DC.
Section 14
1MRK 511 401-UUS A
Control
398
Bay control REC670 2.2 ANSI
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...