command output pulse remains active until the timer
tOpenPulsetClosePulse
has
elapsed.
tOpenPulse
is the output pulse length for an open command. If
AdaptivePulse
is set to
Adaptive
, it is the maximum length of the output pulse for an open command. The
default length is set to 200 ms for a circuit breaker (SXCBR) and 500 ms for a
disconnector (SXSWI).
tClosePulse
is the output pulse length for a close command. If
AdaptivePulse
is set to
Adaptive
, it is the maximum length of the output pulse for an open command. The
default length is set to 200 ms for a circuit breaker (SXCBR) and 500 ms for a
disconnector (SXSWI).
14.3.3.4
Proxy for signals from switching device via GOOSE XLNPROXY
GUID-7C253FE7-6E02-4F94-96C7-81C9129D925D v1
The
SwitchType
setting controls the evaluation of the operating capability. If
SwitchType
is set to
Circuit Breaker
, the input OPCAP is interpreted as a breaker
operating capability, otherwise it is interpreted as a switch operating capability.
Table 36:
Operating capability values for breaker/switches
Value
Breaker operating capability, CbOpCap
Switch operating capability, SwOpCap
1
None
None
2
Open
Open
3
Close – Open
Close
4
Open – Close – Open
Close and Open
5
Close – Open – Close – Open
Larger values handled as 4, both Close and
Open
6
Open – Close – Open – Close – Open
7
more
tStartMove
is the supervision time for the apparatus to start moving after a command
execution is done from the SCSWI function. When the time has expired, the command
supervision is reset, and a cause-code is given.
During the
tIntermediate
time, the position indication is allowed to be in an
intermediate (00) state. When the time has expired, the command supervision is reset,
and a cause-code is given. The indication of the mid-position at SCSWI is suppressed
during this time period when the position changes from open to close or vice-versa if
the parameter
SuppressMidPos
is set to
On
in the SCSWI function.
In most cases, the same value can be used for both
tStartMove
and
tIntermediate
as in
the source function. However,
tStartMove
may need to be increased to accommodate
for the communication delays, mainly when representing a circuit breaker.
1MRK 511 401-UUS A
Section 14
Control
Bay control REC670 2.2 ANSI
369
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...