Table 767: Electromagnetic compatibility tests
Description
Type test value
Reference
1 MHz/100 kHz burst disturb-
ance test
IEC 61000-4-18
IEC 60255-26
IEEE C37.90.1-2012
• Common mode
2.5 kV
• Differential mode
2.5 kV
3 MHz, 10 MHz and 30 MHz
burst disturbance test
IEC 61000-4-18
IEC 60255-26
• Common mode
2.5 kV
Electrostatic discharge test
IEC 61000-4-2
IEC 60255-26
IEEE C37.90.3-2001
• Contact discharge
8 kV
• Air discharge
15 kV
Radio frequency interference
test
10 V (rms)
IEC 61000-4-6
f = 150 kHz...80 MHz
IEC 60255-26
10 V/m (rms)
IEC 61000-4-3
f = 80...2700 MHz
IEC 60255-26
10 V/m
ENV 50204
f = 900 MHz
IEC 60255-26
20 V/m (rms)
IEEE C37.90.2-2004
f = 80...1000 MHz
Table continues on the next page