time of installation and commissioning and not change it throughout the
protection relay's service. Changing the
SG operation mode setting from
"Logic mode 1" to "Logic mode 2" or from "Logic mode 2" to "Logic mode
1" does not affect the setting group (SG).
For example, six setting groups can be controlled with three binary inputs. The
SG
operation mode is set to “Logic mode 2” and inputs
BI_SG_2
and
BI_SG_5
are
connected together the same way as inputs
BI_SG_3
and
BI_SG_6
.
Table 36: SG operation mode = “Logic mode 1”
Input
BI_SG_2
BI_SG_3
BI_SG_4
BI_SG_5
BI_SG_6
Active group
FALSE
FALSE
FALSE
FALSE
FALSE
1
TRUE
FALSE
FALSE
FALSE
FALSE
2
any
TRUE
FALSE
FALSE
FALSE
3
any
any
TRUE
FALSE
FALSE
4
any
any
any
TRUE
FALSE
5
any
any
any
any
TRUE
6
Table 37: SG operation mode = “Logic mode 2”
Input
BI_SG_2
BI_SG_3
BI_SG_4
BI_SG_5
BI_SG_6
Active group
FALSE
FALSE
FALSE
any
any
1
TRUE
FALSE
FALSE
any
any
2
any
TRUE
FALSE
any
any
3
any
any
TRUE
FALSE
FALSE
4
any
any
TRUE
TRUE
FALSE
5
any
any
TRUE
any
TRUE
6
The setting group 1 can be copied to any other or all groups from HMI (Copy group
1).
3.7
Test mode
3.7.1
Function blocks
1MRS758755 C
Basic functions
REC615 & RER615
Technical Manual
75