
Table 716: PHQVVR Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Phase supervision
1=Ph A
2=Ph B
3=Ph A + B
4=Ph C
5=Ph A + C
6=Ph B + C
7=Ph A + B + C
7=Ph A + B + C
Monitored voltage
phase
Phase mode
1=Three Phase
2=Single Phase
2=Single Phase
Three/Single phase
mode
10.3.9
Monitored data
10.3.9.1
PHQVVR Monitored data
Table 717: PHQVVR Monitored data
Name
Type
Values (Range)
Unit
Description
ST_A
BOOLEAN
0=False
1=True
Start Phase A
(Voltage Varia-
tion Event in pro-
gress)
ST_B
BOOLEAN
0=False
1=True
Start Phase B
(Voltage Varia-
tion Event in pro-
gress)
ST_C
BOOLEAN
0=False
1=True
Start Phase C
(Voltage Varia-
tion Event in pro-
gress)
INSTSWELLCNT
INT32
0...2147483647
Instantaneous
swell operation
counter
MOMSWELLCNT INT32
0...2147483647
Momentary swell
operation coun-
ter
TEMPSWELLCNT INT32
0...2147483647
Temporary swell
operation coun-
ter
MAXDURS-
WELLCNT
INT32
0...2147483647
Maximum dura-
tion swell opera-
tion counter
INSTDIPCNT
INT32
0...2147483647
Instantaneous
dip operation
counter
Table continues on the next page
1MRS758755 C
Power quality measurement functions
REC615 & RER615
Technical Manual
723
Содержание Relion REC615
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......