A) Three phase mode
B) Single phase mode
Figure 367: Concurrent dip and two-phase swell
10.3.5
Recorded data
Besides counter increments, the information required for a later fault analysis is
stored after a valid voltage variation is detected.
Recorded data information
When voltage variation starts, the phase current magnitudes preceding the
activation moment are stored. Also, the initial voltage magnitudes are temporarily
stored at the variation starting moment. If the variation is, for example, a two-
phase voltage dip, the voltage magnitude of the non-active phase is stored from
this same moment, as shown in
. The function tracks each variation-
1MRS758755 C
Power quality measurement functions
REC615 & RER615
Technical Manual
717