9.1.9
Technical revision history
Table 658: CBXCBR Technical revision history
Technical revision
Change
B
Interlocking bypass input (
ITL_BYPASS
)
and opening enabled (
OPEN_ENAD
)/clos-
ing enabled (
CLOSE_ENAD
) outputs added.
ITL_BYPASS
bypasses the
ENA_OPEN
and
ENA_CLOSE
states.
C
Internal improvement.
D
Added inputs
TRIP
and
SYNC_OK
. Renamed
input
ITL_BYPASS
to
SYNC_ITL_BYP
.
Added outputs
CL_REQ
and
OP_REQ
. Out-
puts
OPENPOS
and
CLOSEPOS
are forced to
“FALSE” in case status is Faulty (11).
Table 659: DCXSWI Technical revision history
Technical revision
Change
B
Maximum and default values changed to 60 s
and 10 s respectively for
Event delay
settings.
Default value changed to 30 s for
Operation
timeout
setting.
C
Outputs
OPENPOS
and
CLOSEPOS
are forced
to “FALSE” in case status is Faulty (11).
9.2
Disconnector position indicator DCSXSWI and
earthing switch indication ESSXSWI
9.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE
C37.2 device
number
Disconnector position indication DCSXSWI
I<->O DC
I<->O DC
Earthing switch indication
ESSXSWI
I<->O ES
I<->O ES
9.2.2
Function block
Figure 311: Function block
Control functions
1MRS758755 C
638
REC615 & RER615
Technical Manual