![ABB Relion REC615 Скачать руководство пользователя страница 62](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253062.webp)
Warning indication
Warning code
Additional information
Unack card comp.
Warning
Protection comm.
50
Error in protection communication.
Warning
ARC1 cont. light
85
A continuous light has been detec-
ted on the ARC light input 1.
Warning
ARC2 cont. light
86
A continuous light has been detec-
ted on the ARC light input 2.
Warning
ARC3 cont. light
87
A continuous light has been detec-
ted on the ARC light input 3.
Warning
RTD card error,X130
96
Temporary error occurred in RTD
card located in slot X130.
Warning
RTD meas. error,X130
106
Measurement error in RTD card loca-
ted in slot X130.
For further information on warning indications, see the operation manual.
3.3
LED indication control
3.3.1
Function block
Figure 12: Function block
3.3.2
Functionality
The protection relay includes a global conditioning function LEDPTRC that is used
with the protection indication LEDs.
LED indication control should never be used for tripping purposes.
There is a separate trip logic function TRPPTRC available in the relay
configuration.
Basic functions
1MRS758755 C
62
REC615 & RER615
Technical Manual
Содержание Relion REC615
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......