Parameter
Values (Range)
Unit
Step
Default
Description
Rated Op current
100.00...5000.00
A
0.01
1000.00
Rated operating
current of the
breaker
Rated fault current 500.00...75000.00
A
0.01
5000.00
Rated fault current
of the breaker
Op number rated
1...99999
1
10000
Number of opera-
tions possible at
rated current
Op number fault
1...10000
1
1000
Number of opera-
tions possible at
rated fault current
Inactive Alm days
0...9999
1
2000
Alarm limit value of
the inactive days
counter
Travel time Clc
mode
1=From Cmd to Pos
2=From Pos to Pos
2=From Pos to Pos Travel time calcu-
lation mode selec-
tion
Table 578: SSCBR Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Opening time Cor
-100...100
ms
1
10
Correction factor
for open travel time
in ms
Closing time Cor
-100...100
ms
1
10
Correction factor
for CB close travel
time in ms
Counter initial Val
0...99999
1
0
The operation num-
bers counter initial-
ization value
Ini Acc currents Pwr 0.00...20000.00
0.01
0.00
Initial value for ac-
cumulation energy
(Iyt)
Life alarm level
0...99999
1
500
Alarm level for CB
remaining life
Pressure alarm
time
0...60000
ms
1
10
Time delay for gas
pressure alarm in
ms
Pres lockout time
0...60000
ms
10
10
Time delay for gas
pressure lockout in
ms
Ini inactive days
0...9999
1
0
Initial value of the
inactive days coun-
ter
Inactive Alm hours
0...23
h
1
0
Alarm time of the
inactive days coun-
ter in hours
7.1.8
Monitored data
7.1.8.1
SSCBR Monitored data
Table 579: SSCBR Monitored data
Name
Type
Values (Range)
Unit
Description
T_TRV_OP
FLOAT32
0...60000
ms
Travel time of
the CB during
Table continues on the next page
Condition monitoring functions
1MRS758755 C
566
REC615 & RER615
Technical Manual