Parameter
Values (Range)
Unit
Step
Default
Description
2=phase-to-phase
phase-to- phase
voltages
Phase supervi-
sion
1=A or AB
2=B or BC
3=A&B or AB&BC
4=C or CA
5=A&C or AB&CA
6=B&C or BC&CA
7=A&B&C or
AB&BC&CA
4=C or CA
Monitored volt-
age phase
Num of phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of pha-
ses required for
voltage supervi-
sion
V live value
0.2...1.0
xUn
0.1
0.5
Limit value for
high voltage
V live time
40...10000
ms
1
100
Duration time for
high voltage
V dead value
0.1...0.8
xUn
0.1
0.2
Limit value for
low voltage
V dead time
40...10000
ms
1
100
Duration time for
low voltage
Table 572: PHSVPR Non group settings (Advanced)
Parameter
Values
(Range)
Unit
Step
Default
Description
Relative hystere-
sis
1.0...5.0
%
0.1
4.0
Relative hysteresis for volt-
age supervision
6.4.8
Monitored data
Table 573: PHSVPR Monitored data
Name
Type
Values (Range)
Unit
Description
PHSVPR
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Supervision functions
1MRS758755 C
550
REC615 & RER615
Technical Manual