![ABB Relion REC615 Скачать руководство пользователя страница 540](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253540.webp)
Name
Type
Default
Description
U_C_CA
SIGNAL
0
Phase C voltage
U
2
SIGNAL
0
Negative phase se-
quence voltage
BLOCK
BOOLEAN
0=False
Block of function
CB_CLOSED
BOOLEAN
0=False
Active when circuit
breaker is closed
DISCON_OPEN
BOOLEAN
0=False
Active when line dis-
connector is open
MINCB_OPEN
BOOLEAN
0=False
Active when external
MCB opens protected
voltage circuit
6.2.6.2
SEQSPVC Output signals
Table 557: SEQSPVC Output signals
Name
Type
Description
FUSEF_3PH
BOOLEAN
Three-phase start of function
FUSEF_U
BOOLEAN
General start of function
6.2.7
Settings
6.2.7.1
SEQSPVC Non group settings
Table 558: SEQSPVC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 559: SEQSPVC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Neg Seq current
Lev
0.03...0.20
xIn
0.01
0.03
Operate level of
neg seq undercur-
rent element
Neg Seq voltage
Lev
0.03...0.20
xUn
0.01
0.10
Operate level of
neg seq overvolt-
age element
Current change
rate
0.01...0.50
xIn
0.01
0.15
Operate level of
change in phase
current
Voltage change
rate
0.25...0.90
xUn
0.01
0.40
Operate level of
change in phase
voltage
Change rate enable 0=False
1=True
0=False
Enabling operation
of change based
function
Table continues on the next page